Experience with Koyo PLC

Hardware specific:

   1 PLC power:

      Direct come from outside, as far away to the signal, at least 12 awg of the ground cable



   2 insulation:

      >10 mohm, 500V DC

   3 Dielectric:

       1500V 1 minutes

   4 24 DC relay maxmum current:


       300 ma

    5 input response time:

            1 to 9 ms

    6 input current:

             4 to 8 ma


    7 input impendence:

         2.7khom to 3.9 hom

    8 sinking:

          DC power negative connect to commom

     9 Sourcing:


           DC power positive connect to common



登录后才可评论.